Legionella Risk Assessment

A legionella risk assessment for a building's hot and cold water system, written for UK landlords, managing agents and facilities teams: the people at risk, a description of the system, the cold water tank, the hot water cylinder or calorifier, a log of outlet temperatures (each one outside its target flagged), little-used outlets, dead legs, showers and empty periods, and the control scheme with the responsible person named.

Free — no account, no trial, no card.

Fill this in and download the finished PDF. Your answers stay on this device as you type. We ask for an email address once, at the download.

0 of 47 answered0%
1

Premises and Assessor

Which building, who is responsible for it, and who assessed it.

Tell me what you seeSign in to talk instead of typing.

The named person who makes sure the control scheme is carried out.

A locked loft or plant room left unchecked should be named, not passed over.

2

People at Risk

Who uses the water, and whether any of them are more vulnerable.

Tell me what you seeSign in to talk instead of typing.
3

The Water System

What supplies the cold, what heats the hot, and where it all goes.

Tell me what you seeSign in to talk instead of typing.

Where the stopcock, tank and heater are; how many outlets; anything unusual.

0/4 · they go into your PDF and stay on this computer

0/4 · they go into your PDF and stay on this computer

4

Cold Water Storage Tank

Covered, clean, cool, and turning over its water.

Tell me what you seeSign in to talk instead of typing.

Answer No and the questions that follow fold away.

5

Hot Water Storage

Stored hot enough to kill the bacteria, and able to be drained and checked.

Tell me what you seeSign in to talk instead of typing.

A combination boiler stores none. Answer No and this section folds away.

6

Outlet Temperatures

One row per tap or shower tested. Any reading outside its target is a finding.

Tell me what you seeSign in to talk instead of typing.

Run each tap and read the thermometer in the flow. Hot outlets: at least 50 °C within one minute. Cold outlets: below 20 °C within two minutes. Start with the outlets nearest to and furthest from the heater or tank.

Temperature readings*

Nothing added yet.

7

Risk Factors

Where water sits still, sprays, or goes unused.

Tell me what you seeSign in to talk instead of typing.

Spa pools and cooling towers need their own specialist assessment and monitoring.

8

Risk Rating and Control Scheme

How risky this system is, what keeps it under control, and who does it.

Tell me what you seeSign in to talk instead of typing.

Keep records for at least five years.

Corrective actions

Nothing added yet.

Sooner if the system, the building's use or its occupants change, or checks show a problem.

Sign above — Assessor
Sign above — Responsible person
Sign above — Duty holder

Free, no account needed. Your answers never leave this browser.

A legionella risk assessment looks at a building's water system and asks where Legionella bacteria could grow and reach someone's lungs: water sitting between 20 °C and 45 °C, water that does not move, and outlets that make a fine spray. In the UK, anyone who controls premises — employers, landlords, managing agents — has a duty to assess that risk and control it, and the Health and Safety Executive's Approved Code of Practice L8 and its guidance HSG274 describe how. This template records the system, the risk factors and the temperatures you actually measured, and flags every reading outside its target. You can fill it in here and download a finished PDF without creating an account.

Who needs one

Any employer or person in control of premises with a water system people use. That includes workplaces, hotels, care homes and schools, and it includes residential landlords: a landlord renting out a flat with a combi boiler still has to consider the risk, even if the assessment is short and the conclusion is that the risk is low.

The law does not require a certificate, and there is no such thing as a "legionella certificate" for a domestic let. What it requires is that the risk is assessed by someone competent, that sensible controls are in place, and that you can show it. A completed, dated assessment with readings is how you show it.

What the temperatures should be

The targets below are the ones commonly used under HSG274. Your written scheme may set its own; use those where it does.

  • Cold water at an outlet — below 20 °C within two minutes of running.
  • Hot water at an outlet — at least 50 °C within one minute of running (55 °C in healthcare premises).
  • Hot water stored in a cylinder or calorifier — at least 60 °C.
  • Hot water returning to a calorifier on a circulating system — at least 50 °C.
  • Cold water in a storage tank — below 20 °C.

Where the risk hides

Most findings come from the same few places. Outlets that are hardly used — a spare bathroom, a cleaner's sink — let water sit warm in the pipe for weeks. Dead legs, lengths of pipe left in place after a fitting was removed, do the same permanently. Showers spray water as a fine mist and collect scale where bacteria can live. Cold water tanks without a proper lid gather dust, insects and worse. Properties left empty between lets let the whole system stagnate.

The form asks about each one. Where something is present and not controlled — no weekly flushing, a lid that does not fit, a dead leg still in place — it becomes a finding with its own corrective action.

Why this form does not say "compliant"

L8 is a code of practice, not a checklist that a building passes. Following it is one way to meet the legal duty; another approach can be just as good if it controls the risk as well. A form that stamped a building "L8 compliant" would be claiming more than one visit can know. This one records what the system is, what was found, what was measured and what has to happen next — which is what an inspector or an insurer will ask to see.

Speak while you walk, and the document writes itself: read each thermometer aloud as you go from tap to tap, and the temperature log fills in, outlet by outlet.

Common questions

Do landlords need a legionella risk assessment?

Yes. Residential landlords in the UK have a duty to assess and control the risk from legionella in the properties they let. For a typical flat or house with a combi boiler and no stored water the assessment is short and the risk is usually low, but it still needs to be done and recorded.

Can I do the assessment myself?

Yes, if you are competent to do it — you understand the water system and the risk factors. Many landlords assess simple domestic properties themselves. Larger or more complex systems, and premises with vulnerable people, usually call for a specialist.

How often should it be reviewed?

The law does not set a fixed interval. Review it regularly, and straight away if the system changes, the use of the building changes, the people using it change, or monitoring shows the controls are not working. Many duty holders review every one to two years.

Do I need to test the water for legionella?

Not routinely in most domestic and simple systems — temperature checks are the usual evidence that control is working. Sampling for bacteria is used in higher-risk systems, such as cooling towers, spa pools and healthcare buildings, or when temperatures cannot be maintained.

What is a sentinel outlet?

The outlets nearest to and furthest from the hot water heater or cold tank on each part of the system. If those reach the right temperatures in time, the rest of that part of the system is likely to as well, which is why monthly checks usually start with them.