A fire pump inspection form for the routine run test — the pump started without water flowing, run for a set time, and watched. It records the readings that tell you whether the pump will deliver when the sprinklers need it: the pressure it started at, suction and discharge pressure while running, speed, run time, packing and bearings, and how the motor or engine behaved. It records what you saw; it does not make a pump compliant with NFPA 25 or any other standard on its own.
What the run test is, and what it is not
In a no-flow or churn test the pump runs against a closed system, with only the small circulation relief flow keeping it cool. It proves the pump starts on falling pressure, comes up to speed, builds pressure and keeps running without overheating, leaking or alarming. It is the frequent, cheap test that catches a seized pump, a flat battery or a closed valve before a fire does.
It is not the annual flow test. That one pushes water through a test header or flow meter at rated and peak flow and compares the result with the pump's curve, and it needs more equipment and usually a specialist contractor. This form says so on the page, and the result question lets you note when the annual test is due.
How often
In the US most jurisdictions adopt NFPA 25 for inspection, testing and maintenance of water-based fire protection. Its run-test frequency depends on the driver (diesel engines are commonly run weekly, electric motors weekly or monthly depending on the edition and the installation) and on what your authority having jurisdiction and your insurer require. Outside the US, local standards and insurers set the interval. Find out which edition your building is held to and write the interval into your own schedule.
Readings worth writing down every time
A tick saying "pump ran OK" tells nobody anything next month. A column of numbers does: a start pressure creeping down shows a jockey pump or pressure switch drifting, a net pressure falling over time shows wear, a bearing running hotter each week shows a problem coming. The ones this form asks for:
- The pressure at which the pump started on its own.
- Suction and discharge pressure while running, and the difference between them.
- Speed, if you have a tachometer or the controller shows it.
- How long it ran, against the minimum your schedule sets.
- Packing gland drip rate, and the hottest bearing temperature.
- For diesels: oil pressure, coolant temperature, battery voltages and the fuel level.
Before you start, and after you finish
Tell the alarm monitoring company the system is going on test, or a pump-running signal can bring the fire department. When you finish, put every valve back, return the controller to automatic, clear the panel and tell the monitoring company you are done. A run test that leaves the controller in manual or a suction valve half shut has made the building less safe than before you arrived, which is why restoring the system has a section of its own.
Common questions
How long should a fire pump run during the test?
Commonly about 10 minutes for an electric motor and 30 minutes for a diesel engine, so the engine reaches working temperature. Use the figure in the edition of the standard your building is held to, or your insurer's, and record the actual run time on the form.
What is a churn test?
Another name for a no-flow test: the pump runs with the system closed, so it produces pressure but almost no flow. It checks starting, running and the driver, not whether the pump still meets its rated flow — that is the annual flow test.
How much should the packing drip?
Packing glands are meant to drip slowly to cool and lubricate the shaft; a common rule of thumb is a steady drip of a few drops a minute. Dry packing can score the shaft, and a stream means it needs adjusting. Mechanical seals should not drip at all.
Who can carry out the run test?
The routine run is often done by trained building staff or facilities engineers; the annual flow test and repairs are usually done by a fire protection contractor. Your local rules or insurer may require a qualified person for either. The form records who did the test and how they are qualified.
What happens if the pump fails the test?
Treat the system as impaired: tell the building owner, the alarm company, the fire department and the insurer as your impairment procedure requires, and put a fire watch or other temporary measures in place until it is repaired. The form asks about this whenever the result is a failure.